Modules · Compliance studies · Module 028
Geomagnetic disturbance planned performance requirements for applicable transformers, documented and evidenced.
About this module
This module develops your compliance procedure for NERC TPL-007-4, Transmission System Planned Performance for Geomagnetic Disturbance (GMD) Events, and applies it at each applicable plant. TPL-007-4 applies to Generator Owners whose Facilities include power transformer(s) with a high-side, wye-grounded winding and terminal voltage greater than 200 kV. It requires benchmark and supplemental thermal impact assessments of applicable BES power transformers based on GIC flow information provided by the PC and TP (benchmark at 75 A per phase or greater, supplemental at 85 A per phase or greater). This module covers development of the compliance procedure and GMD thermal impact assessments for each applicable plant.
Module: 028
Kind: Compliance studies
Governing body: NERC
Applies to: Operating plants
Typical time: About one week, all in