ISO-NE Model Quality Tests

The ISO-NE Planning Procedure 5-6 Appendix C-2 test battery at short circuit ratios 3 and 10, run on your PSCAD and PSS/E models.

About this module

What this module covers.

ISO-NE requires model quality tests (MQT) for inverter-based resources (IBRs), per Planning Procedure 5-6 (PP5-6) Appendix C-2. This module conducts the required ISO-NE MQT studies to validate your dynamic models against ISO-NE performance criteria. Appendix C-2 requires most tests to run at both short circuit ratio (SCR) 3 and SCR 10, so this is a larger battery than a single-strength suite; energy storage plants repeat each case in charging mode at submission time.

At a glance

Module: 067
Kind: Modeling studies
Governing body: ISO-NE
Applies to: Before and after commercial operation
Typical time: Two to three weeks, all in, including your review

Dashboard capabilities

  • Model Workspace Management: your plant's simulation model files kept in one dashboard workspace, with version tracking
  • PSCAD Simulations
  • PSS/E Simulations

Support services

What GridStrong does inside this module.

  • Perform all required ISO-NE Model Quality Tests (44 tests across SCR 3 and SCR 10; full list below).
    • Benchmark results across PSCAD and PSS/E models.
    • Coordinate with original equipment manufacturers (OEMs) on modeling deficiencies identified during testing.
    • Prepare the MQT report for your submission to ISO-NE.

Tests: Steady state / capability

  • Flat Run (Pnet, Q0) and (0.5 Pnet, Q0)
  • PSS/E flat start (20 s) and ring-down (60 s)
  • Steady-state Q limit (Pnet/P0 x Qmax/Qmin) - 4 cases
  • Dynamic Q limit (V step up / down)

Tests: Reference steps (at SCR 3 and SCR 10)

  • Vref step +/-2%
  • Pref step +/-10%
  • Frequency step +/-0.3 Hz

Tests: Fault ride-through (FRT) (at SCR 3 and SCR 10)

  • Balanced FRT 2x3-phase bolted (Pnet and 0.5 Pnet)
  • Balanced FRT at IBR collector bus (HVDC-connected)
  • Balanced remote FRT (66% V)
  • Unbalanced FRT single-line-to-ground, 15 cycles

Tests: Protection & ride-through curves

  • Voltage protection verification (over / under voltage)
  • PRC-024 low- and high-voltage ride-through (LVRT and HVRT) curves at the point of interconnection (POI)
  • Low / High frequency ride-through composite

Tests: Grid disturbance (at SCR 3 and SCR 10)

  • Rate of change of frequency (ROCOF) 5 Hz/s, 60 to 59 Hz
  • Phase angle jump +/-25 deg
  • POI SCR transition + 3-phase fault at each transition

Final deliverables

  • ISO-NE MQT report including results from all required tests at both system strengths.
  • Updated PSCAD and PSS/E simulation models where applicable (charged under the related modules).

What we need from you

  • Latest PSCAD and PSS/E simulation models including collector system, main power transformer, power plant controller, and all necessary control and protection.
  • Single-line diagram of the plant.
  • PRC-024 voltage and frequency ride-through settings.
  • User manuals and OEM documentation.

Assumptions and considerations

How the scope is bounded.

  • Most tests run at both SCR 3 and SCR 10 per C-2 Section 1.1.3.
  • Energy storage plants repeat each case in charging mode (negative POI real power) at submission.
  • You supply all required models and site documentation.