Modules · Event analysis · Module 082
Qualifying changes in your plant's real power output detected, and the event analysis and corrective action plans tracked to closure.
About this module
PRC-030-1, effective October 1, 2026, requires Generator Owners of inverter-based resources (IBRs) to identify, analyze, and mitigate unexpected changes in power output. Generator Owners must implement a documented process to detect any complete facility loss or real power output change of at least 20 megawatts (MW) and at least 10% of the plant's gross nameplate rating within a 4-second period, excluding changes due to intermittent resource variability, planned outages, or certain system misoperations. When such an event occurs, the Generator Owner has 90 days to analyze the event, determine root causes, document ride-through and reactive power response, assess performance issues, and determine whether the findings apply to other facilities. If corrective actions are needed, a Corrective Action Plan (CAP) or a technical justification must be developed within 60 days, provided to the relevant reliability entities, and updated as necessary, with all actions and communications documented and retained for compliance purposes.
This module covers the preparation of compliance procedures and assessment documentation for PRC-030-1, with qualifying events detected from your plant data and carried through the compliance workflow.
Module: 082
Kind: Event analysis
Governing body: NERC
Applies to: Operating plants
Typical time: Days per event, not weeks